Interpret Status Indicators for your FLEX I/O Module

Use the following table to determine the indicator conditions and status.

When an active indicator (yellow) is lighted, a valid signal (active high or active
low) is present at the input terminals.

The module power/status indicator (OK) shows power applied to the module,
and the status of the module.

Status Indicator Identification

Indicator

State

Status

A (status of input A)

Yellow

Input A active.

Off

Input A not active.

B (status of input B)

Yellow

Input B active.

Off

Input B not active.

Z (status of input Z)

Yellow

Input Z active.

Off

Input Z not active.

Out O, 1, 2, 3

Yellow

Output is on.

Off

Individual output is off.

Power/Status Indicator Interpretation

Indicator

State

Status

OK

Solid red

Hardware diagnostic error, TF set to 1 and

module/channel status contains error code.

Hardware runtime failure (that is, watchdog timeout),

module communication ceases.

Flashing red

Module is configuring hardware, NR is set to 1.

Module is in test mode (bits 8…15 of counter control

word are nonzero), TF set to 1.

Flashing red
(with occasional
flashing green)

Module 24V power is below minimum rating.

Solid green

Module is active and acting normally.

Flashing green

Module is not configured.

Programming error, PE is set to 1 and error code is

supplied in bits 0…11 of module/channel status word.

Field power fault, FP set to 1.

Adapter powered down, and module local power

still active.

ControlNet cable disconnected.

PLC in PROG mode.