Period/Rate and Continuous/Rate Output Operation with Scaler of 1

Rate Measurement Mode

Use the rate measurement mode to count incoming pulses for a user-specified
time interval. At the end of the interval, the module returns a value representing
the sampled number of pulses and a value indicating the incoming frequency.
When the count and frequency are updated, any associated outputs are checked
against their associated presets.

The value representing the total number of pulses is returned in input file words 4
(LSW) and 5 (MSW) for channel 0 and 6 (LSW) and 7 (MSW) for channel 1,
and the value indicating the incoming frequency is returned in words 0 (LSW)
and 1 (MSW) and 2 (LSW) and 3 (MSW). The total count equals the running
sum of the number of pulses received during the sample period. The operation of
rate measurement mode is shown in Figure

Operation of the Rate Measurement

Mode on page 12

.

Incoming pulse train at Z
(gate/reset terminal)

5 MHz internal clock

A (not used)

B (not used)

Input A

Input B

Z

Encoder/Pulse generator

1794-VHSC

Input Z

(Gate/Reset)

scaler
5 MHz clock

1

Accumulated count

Outputs updated continuously

Frequency
updated here

10

20

Assumes symmetrical pulse, 50% duty cycle, so period = sample time on X 2 (on and off)
Frequency = 1/period
If count = 25, scaler = 1, and clock period = (1/5 MHz)
Frequency = 1 / [(25/1) X (1/5 MHz) X 2] = 100 KHz