Interpret Status Indicators for your FLEX I/O Module

Diagnostic Codes Returned
by the Module

If an incomplete, incorrect or conflicting set of configuration parameters are sent
to the module, the PE bit is asserted, the green module status indicator flashes,
and an error code is displayed in bits 0…11 of the module/channel status word.
These codes are identified below.

During hardware self-tests, when either FlexBus power or terminal base power is
first applied and a fatal error occurs, the TF bit is asserted and the red module
status indicator turns on. An error code is placed in the lower byte of the
module/channel status word to indicate the failed resource.

Chapter Summary

This chapter described how to troubleshoot your adapter module by interpreting
the status indicators and module/channel status word error codes.

Diagnostics Reported by Input Data Word 8

Read Word

Bit

Indication

Word 8

00

A reserved configuration or mode was programmed.

01

ZF/BF/AF were selected and no filter was programmed, or multiple
filters were selected.

02

A timebase was entered that was not a multiple of 10, or the timebase is
out of range (>3000, that is 3 s).

03

A configuration requiring a timebase was selected and no gate interval
was set, or the gate interval is out of range (>3 s) or the product of
timebase and gate interval is greater than 3 s.

04

A rollover of zero was programmed through PWM was not selected; a
rollover was programmed and PWM was selected; or the rollover is out
of range (1

rollover

16,777,216).

Word

05

The preset (1

preset

16,777,216) is out of range.

06

A configuration was selected that requires a scalar, and no scalar was
programmed or multiple scalars were selected.

07

A tie has been connected to an unprogrammed window.

08

Counter 0 window ON and OFF values are equal and not zero or counter
0 window ON and OFF value greater than 16,777,215.

09

Counter 1 window ON and OFF values are equal and not zero or counter
1 window ON and OFF value greater than 16,777,215.

10

Reserved

11

Error Code Definitions

Read Word

Bit

02

01

00

Dec. Definition

Word 8

00…07

0

0

1

1

RAM test failed.

0

1

0

2

ROM checksum test failed.

0

1

1

3

EEPROM test failed.

1

0

0

4

Programmable Gate Array
loading failed

All other combinations not used.