Install Your FLEX I/O VHSC Module

Wiring Information

This section provides essential wiring information for the 1794-TB3G, 1794-
TB3GK, and 1794-TB3GS terminal base units. It also includes instructions for
connecting wiring to the FLEX I/O module.

Wire the Terminal Base Units (1794-TB3G shown)

Wiring the FLEX I/O VHSC Input module is done using the 1794-TB3G,
1794-TB3GK or the 1794-TB3GS terminal base unit.

IMPORTANT

The adapter is capable of addressing eight modules. Do not exceed a
maximum of eight terminal base units in your system.

Digital input

module

Digital input

module

Digital output

module

VHSC

module

VHSC

module

Frequency input

module

VHSC

module

VHSC

module

Daisy-chaining

Individual

24V DC

24V DC

24V DC

24V DC

Wiring when total current draw is less than 10 A

Wiring when total current draw is greater than 10 A

Note: Do not use any digital modules in this configurations.

Note: Use this configuration if using any digital output
modules that could couple transients to the 24V supply.

1794-VHSC module wiring separate from digital wiring.

45897

ATTENTION: Take note of the following considerations when wiring
your terminal base units:

·

AIl modules must be frequency or analog modules for the daisychain
configuration.

·

Use the individual type of configuration for any "noisy" DC digital I/O
modules in your system.

·

All modules powered by the same power supply must be frequency or
analog modules for the combination type of configuration.