The adapter input status word bit descriptions are show in Table

Input Status

Word Bits on page 32

.

Possible causes for an I/O module fault are:

• transmission errors on the FLEX I/O backplane
• a failed module
• a module removed from its terminal base
• an incorrect module inserted in a slot position
• an empty slot
• a non-discrete module in the slot

Safe State Data

The EtherNet/IP adapter does not provide storage for alternate module output
data during communication faults or processor idle state. This safe state data is
stored in the 1794-VHSC module and may be defined using configuration
software. Safe state data assures that a known output will be applied to the output
devices to maintain a previously designated safe operating condition during the
previously mentioned failure modes. This data is sent in the configuration block.
For more information, Table

1794-VHSC — High Speed Counter Module

Image Table Mapping on page 35

.

Device Actions

Device actions include:

• communication fault behavior
• idle state behavior
• input data behavior upon module removal

Input Status Word Bits

Bit Description

Bit

Explanation

I/O Module Fault

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node address
changed

8

This bit is set (1) when the node address switch setting is changed
since power up.

I/O state

9

Bit = 0 – idle
Bit = 1 – run

10…15

Not used – set to 0.