A-2 Specifications

Physical Specifications

Environmental
Specifications

Description

Specification

LED Indicators

5 green status indicators
one for each group of 4 channels,
and one for module status

Module ID Code

Class 1

Class 3

NI16V

3505

10406

NI16I

3504

10403

Recommended Cable

Belden #8761 or equivalent

Maximum Wire Size

Two 14 AWG wires per terminal

Maximum Cable
Impedance

NI16V

Voltage Source (with less than 10

impedance): 1250

maximum loop impedance, for 1LSB error

NI16I

Current Source (transmitter properly wired to its power
supply): 249

maximum loop impedance, to meet

common-mode voltage requirements

Terminal Block

Removable, Allen-Bradley spare part Catalog Number
1746-RT25G

Allen-Bradley Prewired
Cables

1492-ACAB005A46, 0.5m (1.6 ft.)
1492-ACAB010A46, 1.0 m (3.3 ft.)
1492-ACAB025A46, 2.5 m (8.2 ft.)
1492-ACAB050A46, 5.0 m (16.4 ft.)

Allen-Bradley User
Terminal Blocks

1492-AIFM8-3
1492-AIFM16-F-3

Description

Specification

Operating Temperature

0°C to +60°C (+32°F to +140°F) in any slot except slot 0

Storage Temperature

-40°C to

+

85°C (-40°F to

+

185°F)

Relative Humidity

5% to 95% (without condensation)

Agency Certification

UL listed
C-UL approved
CE compliant for all applicable directives

Hazardous Environment
Classification

Class I Division 2 Hazardous Environment