Publication 1746-UM001A-US-P

6-6 Module Diagnostics and Troubleshooting

Troubleshooting Flowchart

Check LEDs

on module.

Module Status

LED off

Module Status

LED on

Channel Status

LED(s) blinking

Channel Status

LED off.

Channel Status

LED on.

Module fault

condition

Fault Condition

Channel is not

enabled.

Channel enabled

and working

properly.

Check to see that
module is seated
properly in chassis.
Cycle power.

End

Check channel

status word

bits 15-13.

Enable channel if desired
by setting channel
configuration word
(Bit 15 = 1). Retry.

End

Status

Bits (15 to

13)

Pattern (011)

Configuration error. Check
configuration word for bits 8 to
6 for valid data format
configuration. Correct and
retry.

Under-range condition exists.
The input signal is less than
the low scale limit for the
channel. Correct and retry.

Is problem
corrected?

Yes

End

Is problem
corrected?

Yes

No

Over-range condition exists.
The input signal is greater than
the upper scale limit for the
channel. Correct and retry.

Contact your

local distributor

or Allen-Bradley.

No

An open-circuit condition is
present. Check channel and
wiring for open or loose
connections. Correct and retry.

Contact your

local distributor

or Allen-Bradley.

Status

Bits (15 to

13)

Pattern (101)

Status

Bits (15 to

13)

Pattern (110)

Status

Bits (15 to

13)

Pattern (100)