Appendix

B

Configuration Worksheet

The following worksheet is provided to help you configure each of
the channels on your module. See Chapter 5 for detailed configuration
information.

11

9

10

8

6

7

4

5

0

1

2

3

12

13

14

15

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit Number

Channel 0

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Class 1 Channel Configuration

Class 1 Handshaking

Input Type

Filter Frequency

Channel Enable

Not Used

Data Format

Calibration

Channel 8

Channel 9

Channel 10

Channel 11

Channel 12

Channel 13

Channel 14

Channel 15

Bit Definitions:

Bit 15

Channel Enable

0 = channel disabled

1 = channel enabled

Bits 14-12 Filter Frequency

000 = 6 Hz
001 = 10 Hz

010 = 20 Hz
011 = 40 Hz

100 = 60 Hz
101 = 80 Hz

110 = 100 Hz
111 = 250 Hz

Bits 11-9

Calibration

000 = exit calibration
(normal run mode)

001 = enter calibration

011 = perform zero
calibration

101 = perform full scale
calibration

Bits 8-6

Data Format

Class 1 and Class 3

Class 3 Only

000 = engineering units
001 = scaled-for-PID

010 = proportional counts
011 = 1746-NI4 data format

100 = user-defined scaling 0
101 = user-defined scaling 1

110 = user-defined scaling 2
111 = user-defined scaling 3

Bits 5-4

Input Type

000 = ±10V dc or ±20 mA
001 = 1-5V dc or 4-20 mA

010 = 0 to 5V dc or 0 to 1 mA
011 = 0 to 10V dc or 0 to 20 mA

Bits 3

Not Used

Bit 2

Class 1
Handshaking

0 = to reset status bit 6

1 = transmit channel configuration

Bits 1-0

Class 1 Data or
Status
Configuration

00 = read data for channels 0 to 7
01 = read data for channels 8 to 15

10 = read status for channels 0 to 7
11 = read status for channels 8 to 15