Channel Configuration, Data, and Status 5-15

1746-NI4 Data Format Units to Real Units

Example: #5 A transducer is being used to measure flow rate.

The -10V dc to +10V dc signal range is proportional to 0 to 100 GPM
The input data is in “1746-NI4” format, i.e. input range of -32768 to 32767
Input value to convert = 10000

The Scaled range is 0 to 100 GPM
The Input range is -32768 to +32767

Find: Input value in GPM

Per the equations above:

User-Defined Scaling Data Format to Real Units

Example: #6 A transducer is being used to measure pressure.

The -10V dc to +10V dc signal range is proportional to 0 to 200 psi
The input data is in “User Defined Format”, where:

The lower input limit (configuration word 8) = 0
The upper input limit (configuration word 9) = 20000

Input value to convert = 16600

Scaled range is 0 to 200 psi
Input range is 0 to 20000

Find: Input value in psi

Per the equation above:

Slope

100

0

(

)

32767

32768

(

)

[

]

------------------------------------------------------

0.0015

=

=

Offset

0

32768

0.0015

×

(

)

49.15

=

=

Scaled Value

10000

0.0015

×

(

)

49.15

64.15 GPM

=

+

=

Slope

200

0

(

)

20000

0

(

)

--------------------------------

0.01

=

=

Offset

0

0

0.01

×

(

)

0

=

=

Scaled Value

16600

0.01

166 psi

=