4 - preliminary operating considerations, Module id code, Chapter 4 – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual

Page 37: Preliminary operating considerations, Module id code -1, Chapter

Advertising
background image

1

Publication 1746-UM001A-US-P

Chapter

4

Preliminary Operating Considerations

This chapter explains how the analog input module and the SLC 500™
processor communicate through the module’s input and output image.
It lists the preliminary setup and operation required before the
module can function in a 1746 I/O system. Topics discussed include
how to:

enter the module ID code

select the Class 1 or Class 3 interface

address your 1746-NI16 module

select the proper input filter for each channel

calculate the module update time

interpret the module response to slot disabling

Module ID Code

The module identification code is a unique number encoded for
each 1746 I/O module. The code defines for the processor the type
of I/O or specialty module residing in a specific slot in the 1746
chassis.

Catalog Number

ID Code

1746-NI16I

Class 1 interface 3504
Class 3 interface 10403

1746-NI16V

Class 1 interface 3505
Class 3 interface 10406

Advertising