Publication 1746-UM001A-US-P

Channel Configuration, Data, and Status 5-19

Class 3 Status Word

Define

To Select

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Class 1
Data or Status
Configuration

Data from Channel 0 to 7

0

0

Data from Channel 8 to 15

0

1

Status for Channel 0 to 7

1

0

Status for Channel 8 to 15

1

1

Input Type

± 10 Vdc or ± 20 mA

0

0

1 to 5 Vdc or 4 to 20 mA

0

1

0 to 5 Vdc or 0 to 1 mA

1

0

0 to 10 Vdc or 0 to 20 mA

1

1

Data Format

Engineering Units

0

0

0

Scaled-for-PID

0

0

1

Proportional Counts

0

1

0

1746-NI4 Data Format

0

1

1

User Limit Range 0

1

0

0

User Limit Range 1

1

0

1

User Limit Range 2

1

1

0

User Limit Range 3

1

1

1

Calibrate
Channel Status

Normal RUN Mode (Exit Calibration Mode)

0

0

0

Calibration Mode Entered

0

0

1

Zero Value Calibrated

0

1

1

Full Scale Calibrated

1

0

1

Filter Frequency
Filter frequencies are
set in ch 0, 4, 8 and 12 for
that channel and the
following 3 channels in
that group.
Filter groupings are:
(0

to

3) (4

to

7) (8

to

11)

and (12

to

15)

6 Hz

0

0

0

10 Hz

0

0

1

20 Hz

0

1

0

40 Hz

0

1

1

60 Hz

1

0

0

80 Hz

1

0

1

100 Hz

1

1

0

250 Hz

1

1

1

Error Conditions

Channel Disabled

0

0

0

Faulty Calibration

0

0

1

Invalid Calibration Reference

0

1

0

Configuration Error

0

1

1

Open-Circuit Detected

1

0

0

Under-Range Detected

1

0

1

Over-Range Detected

1

1

0

No Error

1

1

1

NOTE

Bits 1 and 0 indicate origin in Class 1 mode. Bits 15
through 2 contain real data for each channel.

If the module is in Class 3 mode, all 16 bits are real
data, depending on the data type.