2-4 Quick Start for Experienced Users
5.
Configure the system.
Reference
Configure your system I/O for the particular slot the 1746-NI16 is in (slot 1 in this example). Enter the module ID
code. The ID code is for Class 1 interface or Class 3 interface. See Chapter 4 for more information on Class 1 and
Class 3 interfaces.
Important: Not all programming software supports configuration for Class 3 operation.
•
Advanced Programming Software (APS) supports Class 3 configuration, after entering the ID code.
•
SLC 500 A.I. Series Programming Software supports Class 3 configuration, after entering the ID code.
•
RSLogix 500, version 1.30 or later, supports Class 3 configuration, after entering the ID code.
•
Earlier versions of RSLogix 500 only supports configuration for Class 1 operation. Contact Rockwell
Software for information on upgrading your software.
Chapter 4
(Preliminary
Operating
Considerations)
Appendix C
(Converting from
1746-NI4 or
1746-NI8 to
1746-NI16)
Device’s user
manual.
6.
Determine the operating parameters.
Reference
11
15
3
2
14
13
12
10
9
8
7
6
5
4
1
0
0
1
0
0
0
1
0
0
0
0
0
0
0
0
0
0
Bit Number
Channel 0
•
Class 1, Data or Status Configuration
•
Input Type: ± 10 V dc
•
Data Format: Engineering Units
•
Filter Frequency: 20 Hz
•
Channel Enable: Enabled
•
Class 1 Handshaking
Chapter 4
(Preliminary Opening
Considerations)
Chapter 5
(Channel
Configuration,
Data and Status)
Appendix B
(1746-NI16
Configuration
Worksheet)
Determine the operating parameters for channel 0. This example shows the channel 0 configuration word. The
module is in slot 1. The default configuration word is all zeros.
•
Calibration
•
Not Used