2-4 Quick Start for Experienced Users

5.

Configure the system.

Reference

Configure your system I/O for the particular slot the 1746-NI16 is in (slot 1 in this example). Enter the module ID
code. The ID code is for Class 1 interface or Class 3 interface. See Chapter 4 for more information on Class 1 and
Class 3 interfaces.

Important: Not all programming software supports configuration for Class 3 operation.

Advanced Programming Software (APS) supports Class 3 configuration, after entering the ID code.

SLC 500 A.I. Series Programming Software supports Class 3 configuration, after entering the ID code.

RSLogix 500, version 1.30 or later, supports Class 3 configuration, after entering the ID code.

Earlier versions of RSLogix 500 only supports configuration for Class 1 operation. Contact Rockwell
Software for information on upgrading your software.

Chapter 4

(Preliminary

Operating

Considerations)

Appendix C

(Converting from

1746-NI4 or
1746-NI8 to

1746-NI16)

Device’s user

manual.

6.

Determine the operating parameters.

Reference

11

15

3

2

14

13

12

10

9

8

7

6

5

4

1

0

0

1

0

0

0

1

0

0

0

0

0

0

0

0

0

0

Bit Number

Channel 0

Class 1, Data or Status Configuration

Input Type: ± 10 V dc

Data Format: Engineering Units

Filter Frequency: 20 Hz

Channel Enable: Enabled

Class 1 Handshaking

Chapter 4

(Preliminary Opening

Considerations)

Chapter 5

(Channel

Configuration,

Data and Status)

Appendix B

(1746-NI16

Configuration

Worksheet)

Determine the operating parameters for channel 0. This example shows the channel 0 configuration word. The
module is in slot 1. The default configuration word is all zeros.

Calibration