Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual

Page 17

Advertising
background image

Publication 1746-UM001A-US-P

Quick Start for Experienced Users 2-3

3.

Insert the 1746-NI16 module into the chassis.

Reference

ATTENTION

!

Never install, remove, or wire modules with power applied to the chassis or devices
wired to the module.

Make sure system power is off; then insert the module into your 1746 chassis.
In this example procedure, local slot 1 is selected. Any slot may be used except 0.

Chapter 3

(Installation and

Wiring)

Top and Bottom

Module Releases

Card

Guide

4.

Connect sensor cable.

Reference

Connect sensor cable to the module’s terminal block.
Important: Follow these guidelines when wiring the module:

Use shielded communication cable (Belden™ 8761) and keep length as short as possible.

Connect only one end of the cable shield to earth ground.

Connect all the shields to the earth ground at the SLC 500™ chassis mounting tab.

Single-ended source commons may be jumpered together at the terminal block.

Channels are not isolated from each other. All analog commons are connected together internally.

Common mode voltage range is ±10.25 volts. The voltage between any two terminals must be less than
20.5 volts.

The module does not provide power for the analog input transmitters or sensors.

Use a power supply that matches the transmitter (sensor) specifications.

Chapter 3

(Installation and

Wiring)

Sensor Cable

Terminal Block

IN 0

IN 2

IN 4

IN 6

IN 1

IN 3

IN 5

IN 7

Analog Com

Analog Com