Procedures, Procedures -2 – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual

Page 16

Advertising
background image

Publication 1746-UM001A-US-P

2-2 Quick Start for Experienced Users

Procedures

1.

Check the contents of shipping box.

Reference

Unpack the shipping box making sure that the contents include:

analog input module (Catalog Number 1746-NI16)

removable terminal block (factory-installed)

Installation Instructions

If the contents are incomplete, call your local Allen-Bradley representative for assistance.

2.

Ensure that your chassis and power supply support the 1746-NI16 module.

Reference

If you are installing the module in a hazardous location, read “Hazardous Location Considerations” on page 3-1.
Review the power requirements of your system to ensure that your chassis supports the module:

If you are combining a 1746-NI16 module with another I/O module in a fixed controller, refer to the I/O
module compatibility table found in Chapter 3.

For modular style systems, calculate the total load on the system power supply using the procedure
described in the

SLC Installation & Operation Manual for Modular Style Controllers (publication 1747-6.2) or

the

SLC 500 Family System Overview (publication 1747-2.30).

The 1746-NI16 backplane current consumption is 125 mA at 5V dc and 75 mA at 24V dc.

Chapter 3

(Installation and

Wiring)

Appendix A

(Specifications)

Advertising