Module Diagnostics and Troubleshooting 6-3

Open-Circuit Detection

An open-circuit test is performed on all enabled channels configured
for 4 to 20 mA input and all enabled channels with voltage
configurations. Whenever an open-circuit condition occurs, the
channel status LED blinks and the condition is reported in bits 15
through 13 of the channel status word. See “Error Codes” on page 6-5.

Possible causes of an open-circuit include:

The sensing device may be broken.

A wire may be loose or cut.

The sensing device may not have been installed on the
configured channel.

If an open circuit is detected, the channel data word reflects input
data as 0 mA in the 4 to 20 mA configuration. For the voltage module,
open-circuit data is displayed for all voltage ranges as the maximum
value readable in that voltage range. See tables on pages 5-9 and 5-10.

LED Indicators

The module has five LEDs. Four of these are channel status LEDs
numbered to correspond to each of the four groups of four input
channels (0 to 3, 4 to 7, 8 to 11, 12 to 15). The fifth is a module status
LED.

INPUT

Channel Status LEDs

Module Status LED

0-3

4-7

8-11

12-15

Analog Voltage

Module Status

Channel Status