Procedures, Procedures -2 – Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules User Manual User Manual

Page 16

Advertising
background image

Publication 1746-UM005B-EN-P - June 2004

2-2 Quick Start for Experienced Users

Procedures

1.

Check the contents of shipping box.

Reference

Unpack the shipping box making sure that the contents include:

Analog I/O module (Catalog Number 1746-Series)

installation instructions (publication 1746-IN008)

If the contents are incomplete, call your local Allen–Bradley representative for assistance.

2.

Determine your power requirements for the modular controller.

Reference

Review the power requirements of your system to see that your chassis supports placement of the
analog module.

For modular style systems, calculate the total load on the system power supply using the
procedure described in the SLC 500 Modular Hardware Style User Manual (publication
1747-UM011) or the SLC 500 Family System Overview (publication 1747-SO001).

For fixed SLC 500 controllers, refer to the SLC 500 Fixed Hardware Style Installation &
Operation Manual
(publication 1747-6.21).

Chapter 3

(Installing and
Wiring Your
Analog Module)

Appendix A

(Specifications)

Catalog Number

Backplane Current Draw

External 24V dc Power

Supply Tolerance

5V (max.)

24V (max.)

1746-NI4

35 mA

85 mA

NA

1746-NIO4I

55 mA

145 mA

NA

1746-NIO4V

55 mA

115 mA

NA

1746-NO4I

55 mA

195 mA

24 ±10% at 195 mA max.

(21.6 to 26.4V dc)

(1)

1746-NO4V

55 mA

145 mA

24 ±10% at 145 mA max.

(21.6 to 26.4V dc)

(1)

(1)

Required for some applications if SLC 24V power is not readily available.

Advertising