Publication 1746-UM005B-EN-P - June 2004

2-6 Quick Start for Experienced Users

6.

Configure system I/O configuration.

Reference

Configure your system I/O configuration for the particular slot the analog module is in. When
assigning an I/O module to a slot location, select the module from the displayed list. If not listed,
select OTHER at the bottom of the list and enter the module’s ID code at the prompt.

Chapter 4

(Module
Operation

and System

Considerations)

Catalog No.

Module ID Code

1746-NI4

4401

1746-NIO4I

3201

1746-NIO4V

3202

1746-NO4I

5401

1746-NO4V

5402

7.

Check that the module is operating correctly.

Reference

Chapter 5

(Testing Your
Module)

ATTENTION

Machine motion during system checkout can be
hazardous to personnel. During all checkout
procedures, you must disconnect all devices which,
when energized, might cause machine motion.

Apply power to the fixed or modular system. The analog module LED (red) should be
illuminated, indicating that the module is receiving 24V dc power.