Labeling and installing the terminal block, Grounding the foil shields and drain wires – Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules User Manual User Manual

Page 34

Advertising
background image

Publication 1746-UM005B-EN-P - June 2004

3-12 Installing and Wiring Your Analog Module

Labeling and Installing the
Terminal Block

The terminal block has a write-on label. Labeling the terminal block
will help ensure that it is installed on the correct module.

Once you have wired your analog module and properly labeled the
terminal block, install the terminal block on the analog module. To
install the terminal block:

1. Align the terminal block with the receptacle.

2. Insert the terminal block and press firmly at the top and bottom

until it is properly secured.

Grounding the Foil Shields
and Drain Wires

You are now ready to earth ground your foil shield and drain wire
from each cable. Do not connect the foil shield or drain wire to the
analog module terminal block. The foil shield and drain wire must be
connected to earth ground, which is not available on the terminal
block. Refer to the illustration on the next page for wiring diagrams of
the analog modules.

SLOT ____ RACK ____

MODULE _____

Note: The black dot on the terminal block
label indicates the position of terminal 0.

Advertising