Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules User Manual User Manual
Page 75
Advertising
Publication 1746-UM005B-EN-P - June 2004
Programming Examples 6-13
Rung 2:2
Scale values in the 0 to 100% range to the
decimal range for the 4–20 mA analog output.
| Below |Above |
| range flag|range flag |
| B3 B3 +SCP––––––––––––––––––––+ |
|––––]/[––––––––]/[––––––––––––––––––––––––––––––––––+SCALE W/PARAMETERS +–|
| 0 1 |Input N7:0| |
| | 0| |
| |Input Min. 0| |
| | | |
| |Input Max. 100| |
| | | |
| |Scaled Min. 6242| |
| | | |
| |Scaled Max. 31208| |
| | | |
| |Scaled Output O:2.0| |
| | | |
| +–––––––––––––––––––––––+ |
| |
Rung 2:3
| |
|–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|
Advertising