Publication 1746-UM005B-EN-P - June 2004

Quick Start for Experienced Users 2-7

Note: The e is the slot number.

8.

Understanding analog inputs.

Reference

Analog inputs convert current and voltage signals into 16–bit (max.) integer values and place
them in the input image for the slot that the analog module resides in.

Chapter 4

(Module
Operation and
System
Considerations)

Address

1746-NI4

1746-NI04I, -NI04V

I:e.0

Input Channel 0

Input Channel 0

I:e.1

Input Channel 1

Input Channel 1

I:e.2

Input Channel 2

I:e.3

Input Channel 3

Voltage/Current Range

Integer Representation

-10V dc to +10V dc

-32,768 to +32,767

0 to 10V dc

0 to 32,767±10V dc

0 to 5V dc

0 to 16, 384

1 to 5V dc

3,277 to 16,384

-20 mA to +20 mA

-16,384 to +16,384

0 to 20 mA

0 to 16,384±20 mA

4 to 20 mA

3,277 to 16,384