Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules User Manual User Manual
Page 21
Publication 1746-UM005B-EN-P - June 2004
Quick Start for Experienced Users 2-7
Note: The e is the slot number.
8.
Understanding analog inputs.
Reference
Analog inputs convert current and voltage signals into 16–bit (max.) integer values and place
them in the input image for the slot that the analog module resides in.
Chapter 4
(Module
Operation and
System
Considerations)
Address
1746-NI4
1746-NI04I, -NI04V
I:e.0
Input Channel 0
Input Channel 0
I:e.1
Input Channel 1
Input Channel 1
I:e.2
Input Channel 2
I:e.3
Input Channel 3
Voltage/Current Range
Integer Representation
-10V dc to +10V dc
-32,768 to +32,767
0 to 10V dc
0 to 32,767±10V dc
0 to 5V dc
0 to 16, 384
1 to 5V dc
3,277 to 16,384
-20 mA to +20 mA
-16,384 to +16,384
0 to 20 mA
0 to 16,384±20 mA
4 to 20 mA
3,277 to 16,384