Publication 1746-UM005B-EN-P - June 2004

Programming Examples 6-7

Using Scale with Parameters (SCP) Instruction

Rung 2:0

Check for below allowable range.

| Below |

| range flag |

| +LES–––––––––––––––+ B3 |

|–+LESS THAN +–––––––––––––––––––––––––––––––––––––––––––––––––( )–––––|

| |Source A I:1.1| 0 |

| | 0| |

| |Source B 14344| |

| | | |

| +––––––––––––––––––+ |

Rung 2:1

Check for above allowable range.

| Above |

| range flag |

| +GRT–––––––––––––––+ B3 |

|–+GREATER THAN +–––––––––––––––––––––––––––––––––––––––––––––––––( )–––––|

| |Source A I:1.1| 1 |

| | 0| |

| |Source B 16383| |

| | | |

| +––––––––––––––––––+ |

Rung 2:2

Turn on the below range alarm output when the analog

input is below the acceptible range.

| Below Below |

| range flag range alarm |

| B3 O:2 |

|––––] [––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––( )––|

| 0 0 |

Rung 2:3

Turn on the above range alarm output when the analog

input is above the acceptible range.

| Above Above |

| range flag range alarm |

| B3 O:2 |

|––––] [––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––( )––|

| 1 1 |

Rung 2:4

| Below |Above Scale |

| range flag |range flag analog input |

| B3 B3 +SCP–––––––––––––––+ |

|––––]/[––––––––]/[–––––––––––––––––––––––––––––––––––––––+SCALE W/PARAMETERS+–|

| 0 1 |Input I:1.1| |

| 0|

|Input Min. 0|

| |

|Input Max. 32767|

| |

|Scaled Min. 100|

| |

|Scaled Max. 500|

| |

|Scaled Output N7:0|

| 0|

+––––––––––––––––––+

Rung 2:5

| |

|–––––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––|