Publication 1746-UM005B-EN-P - June 2004

2-4 Quick Start for Experienced Users

Make sure system power is off; then insert the analog module into your 1746 chassis. In this
example procedure, local slot 1 is selected.

Card Guide

Top and Bottom Module
Release(s)

5.

Wire the module.

Reference

Important: Follow these guidelines when wiring the module.

Use shielded communication cable (Belden 8761) and keep length as short as possible.

Connect only one end of the cable shield to earth ground.

Channels are not isolated from each other. All analog commons are connected together
internally.

The module does not provide power for analog inputs.

Use a power supply that matches the transmitter (sensor) specifications.

Chapter 3

(Installing and
Wiring Your
Analog Module)