2-4 Quick Start for Experienced Users
Make sure system power is off; then insert the analog module into your 1746 chassis. In this
example procedure, local slot 1 is selected.
Card Guide
Top and Bottom Module
Release(s)
5.
Wire the module.
Reference
Important: Follow these guidelines when wiring the module.
•
Use shielded communication cable (Belden 8761) and keep length as short as possible.
•
Connect only one end of the cable shield to earth ground.
•
Channels are not isolated from each other. All analog commons are connected together
internally.
•
The module does not provide power for analog inputs.
•
Use a power supply that matches the transmitter (sensor) specifications.