Publication 1746-UM005B-EN-P - June 2004

6-16 Programming Examples

Using Standard Math

Rung 2:0

N7:0 contains the percentage of the valve open.

| Check for |

| below range |

| +LES–––––––––––––––+ B3 |

|–+LESS THAN +––––––––––––––––––––––––––––––––+––( )–––––––––––––––––+–|

| |Source A N7:0| | 0 | |

| | 0| | | |

| |Source B 90| | | |

| | | | | |

| +––––––––––––––––––+ | | |

| | +MOV–––––––––––––––+ | |

| +–+MOVE +–+ |

| |Source 6242| |

| | | |

| |Dest O:2.0| |

| | | |

| +––––––––––––––––––+ |

Rung 2:1

| Check for |

| above range |

| +GRT–––––––––––––––+ B3 |

|–+GREATER THAN +––––––––––––––––––––––––––––––––+––( )–––––––––––––––––+–|

| |Source A N7:0| | 1 | |

| | 0| | | |

| |Source B 100| | | |

| | | | | |

| +––––––––––––––––––+ | | |

| | +MOV–––––––––––––––+ | |

| +–+MOVE +–+ |

| |Source 31208| |

| | | |

| |Dest O:2.0| |

| | | |

| +––––––––––––––––––+ |

Ladder logic continued on the next page .