Chapter 2 - safe torque-off connector data, Safe torque-off connector pinout, Chapter 2 – Rockwell Automation 2099-BMxx-S Kinetix Safe Torque-off Feature Safety Reference Manual User Manual

Page 15: Safe torque-off connector data, Safe torque-off connector pinout o, Chapter

Advertising
background image

Rockwell Automation Publication GMC-RM002F-EN-P - June 2013

15

Chapter

2

Safe Torque-off Connector Data

This chapter provides safe torque-off (STO) connector, header, and interface
cable information for the Kinetix 6000 and Kinetix 7000 safe torque-off drives.

Safe Torque-off Connector
Pinout

Headers are available to extend the 9-pin safe torque-off (STO) connector
signals for use in wiring single and multiple safe torque-off drive configurations,
or to defeat (not use) the safe torque-off function.

Table 3 - 9-pin Safe Torque-off (STO) Connector

Topic

Page

Safe Torque-off Connector Pinout

15

Safe Torque-off Header Configurations

17

Safe Torque-off Accessories

20

Safe Torque-off

(STO) Connector Pin

Also Applies to These

STO Connector Headers

Description

Signal

1

Wiring plug header used in

single-drive applications

First-drive wiring header

(2090-XNSM-W) used in
multiple-drive applications

One side of the normally-closed monitoring contact of relay 2

FDBK2+

2

Other side of the normally-closed monitoring contact of relay 2

FDBK2-

3

One side of the normally-closed monitoring contact of relay 1

FDBK1+

4

Other side of the normally-closed monitoring contact of relay 1

FDBK1-

5

Safety enable 2 input

SAFETY ENABLE2+

6

Return for safety enable power (both inputs)

SAFETY ENABLE-

7

Safety enable 1 input

SAFETY ENABLE1+

8

Wiring plug header
Motion-allowed jumper

Output power for continuous enable of the safety function, 500 mA, max

24V+

9

Output power return used for continuous enable of safety function

24V_COM

IMPORTANT

Pins STO-8 (internal 24V+ supply) and STO-9 (24V_COM) are used only by the
motion-allowed jumper to defeat the safe torque-off function. When the safe
torque-off function is in operation, the 24V supply must come from an external
source.

Advertising