This chapter provides safe torque-off feature specifications for your Kinetix 6000
and Kinetix 7000 drives.

Safe Torque-off Response
Time Specifications

The system reaction time is the amount of time from a safety-related event as
input to the system until the system is in the safe state. Faults within the system
can also have an effect upon the reaction time of the system. The safe torque-off
response time for the Kinetix 6000 and Kinetix 7000 safe torque-off drives is
25 ms. This is the time from change of state at the drive input to change of state at
the drive output.

Safe Torque-off Signal
Specifications

To maintain safety rating, Kinetix 6000 and Kinetix 7000 drives must be
installed inside protected control panels or cabinets appropriate for the
environmental conditions of the industrial location. The protection class of the
panel or cabinet should be IP54 or higher.

Kinetix 6000 (series A and B) and Kinetix 7000 Servo Drives

Table 8 - Relay Coil Specifications for the ENABE Signals

Topic

Page

Safe Torque-off Response Time Specifications

29

Safe Torque-off Signal Specifications

29

ATTENTION: The safe torque-off response time is typical of drive performance.
Actual system response time will vary depending on your application.

Attribute

Nom

Min

Max

Pull-in Voltage

24V

18V

26.4V

Drop-out Voltage

0V

2.4V

Coil Resistance

720

648

792

Coil Current

33.3 mA

55.0 mA

Pull-in Time

25 ms

Drop-out Time

20 ms