Safe torque-off wiring requirements – Rockwell Automation 2099-BMxx-S Kinetix Safe Torque-off Feature Safety Reference Manual User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication GMC-RM002F-EN-P - June 2013

Chapter 3 Wiring Your Kinetix Safe Torque-off Drive

Safe Torque-off Wiring
Requirements

These are the safe torque-off (STO) wiring requirements. Wire should be copper
with 75

°C (167 °F) minimum rating.

Table 7 - Safe Torque-off (STO) Connector

Refer to

Appendix B

beginning on

page 31

for Kinetix 6000 and Kinetix 7000

interconnect diagrams with other Allen-Bradley safety products.

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the
values and methods provided.

Safe Torque-off (STO) Connector

Recommended Wire Size

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

Pin

Signal

Stranded Wire

with Ferrule
mm

2

(AWG)

Solid Wire
mm

2

(AWG)

STO-1

STO-2

STO-3

STO-4

STO-5

STO-6

STO-7

STO-8

STO-9

FDBK2+

FDBK2-

FDBK1+

FDBK1-

SAFETY ENABLE2+

SAFETY ENABLE-

SAFETY ENABLE1+

24V +

24V_COM

0.75 (18)

1.5 (16)

7.0 (0.275)

0.235 (2.0)

IMPORTANT

Pins STO-8 (internal 24V+ supply) and STO-9 (24V_COM) are used only by the
motion-allowed jumper to defeat the safe torque-off function. When the safe
torque-off function is in operation, the 24V supply must come from an external
source.

IMPORTANT

To be sure of system performance, run wires and cables in the wireways as
established in the user manual for your drive.

Refer to

Additional Resources

on

page 8

for the appropriate publication.