European Hazardous Location Approval

The following applies when the product bears the Ex Marking.

This equipment is intended for use in potentially explosive atmospheres as defined

by European Union Directive 94/9/EC and has been found to comply with the

Essential Health and Safety Requirements relating to the design and construction

of Category 3 equipment intended for use in Zone 2 potentially explosive

atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements has been assured

by compliance with EN 60079-15 and EN 60079-0.

ATTENTION

This equipment is not resistant to sunlight or other sources of

UV radiation.

WARNING

This equipment must be installed in an enclosure providing at

least IP54 protection when applied in Zone 2 environments.

This equipment must be used within its specified ratings

defined by Rockwell Automation.

Provision must be made to prevent the rated voltage from

being exceeded by transient disturbances of more than 140%

of the rated voltage when applied in Zone 2 environments.

This equipment must be used only with ATEX certified

backplanes.

Secure any external connections that mate to this equipment

by using screws, sliding latches, threaded connectors, or other

means provided with this product.

Do not disconnect equipment unless power has been removed

or the area is known to be nonhazardous.

This equipment must be mounted in an ATEX certified

enclosure with a minimum ingress protection rating of at least

IP54 (as defined in IEC60529) and used in an environment of

not more than Pollution Degree 2 (as defined in IEC 60664-1)

when applied in Zone 2 environments. The enclosure must

utilize a tool removable cover or door.