Troubleshoot the Module Chapter 4
Backplane Status Indicator
State
Probable Cause
Off
Device is not powered - check module status (MS) indicator
Flashing Red
Recoverable fault has occurred
One or more connections have timed-out
Applies to ControlNet and XM Bus connections
Solid Red
Unrecoverable fault has occurred:
•
adapter is "bus off"
•
adapter has failed its duplicate MAC ID check
Flashing Green
Adapter on-line with no connections established
Solid Green
Adapter on-line with connections established (normal
operation, in run mode)