Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 31
Publication ICM-UM001C-EN-E - March 2013
31
Configure the Adapter Chapter 3
The New Module dialog box opens.
4. From the General tab, enter the following information.
5. Click OK to close the dialog box.
On this tab
In this field
Enter
General
Name
Enter a unique name for the module.
Node Address
Enter the node address of the module. This number and the dip
switches on the module must match.
DIP switches 5 through 10 set the module’s node address using
binary addressing.
We recommend that you set the node address to the position of
the module. For example, the module next to the adapter is node
address 1. If there are two module between this module and the
adapter, the node address is 3.
Refer to the XM Dynamic Measurement Module User Manual,
publication
ICM-UM002
, for more information about the dip
switches.