Carlo Gavazzi PQT-90 User Manual

Page 10

Advertising
background image

Logging variables selection and dmd power calculation

This window allows the user to enable the variables to be
logged (Max 8) in the data memory of PQT-90 and the work-
ing mode of this operation.
[1] Select the variables to be logged (Max8) activating the
relevant check boxes.
[2] Select if, in addition to the logging of the average values of the
variables, PQT-90 is required to log also the min and max values in
the time interval.
[3] Select the value of the logging time interval (from 1 to 60 min.)

During the measurement, the instrument takes sam-
ples of the selected variables every 200ms approx; at
the expiry of the set time interval, the instrument cal-
culates the average of the samples and carries out the

data logging. The historical value will therefore be guaranteed
to be highly accurate.
[4] Selects the dmd (W-VA-var-PF) calculation method
between FIXED and FLOATING.

FIXED SELECTION: if a value of 15 minutes is selected, the

PQTSoft Remote

Configuration

Data Logging and relevant duration

29

53

17

PQTSoft Remote

16

Configuration

8

1

2

3

4

5

instrument calculates the dmd value and updates it every 15 minutes.
FLOATING SELECTION: if for example the value “15 minutes” is
selected, the instrument calculates the dmd value and updates
its value at first after 15 minutes and then every minute generat-
ing a window whose width corresponds to 15 minutes and shifts
by units of 1 minute.

The following diagrams show the two working methods.

FIXED DMD POWER CALCULATION

FLOATING DMD POWER CALCULATION

Where: Pmax is the maximum measured power,

Pc is the contractual power
t1 is the selected average period