Digital output alarm setup

[1] Selects the alarm working mode for the digital output.
[2] Selection of activation or deactivation of the event log-
ging of PQT-90.
[3] Selects the variable to be checked. Click the pointer of the
“Variable to be (controlled)” drop-down menu.
Selects the scale and decimal point. Click the pointer of
the “Scale and decimal point” drop-down menu.
[4] Selects the alarm type: selecting the “up-alarm” the alarm is
activated when the selected variable increases above the activa-
tion set-point; “Down alarm” the alarm is activated when the
selected variable decreases below the activation set-point.
[5] Activation setpoint: the alarm is activated when the vari-
able increases above this value.
Deactivation setpoint: the alarm is deactivated when the
variable decreases below this value.
Delay on the activation: selects the minimum delay of the
event on the alarm activation.
[6] Chooses the normal status of the output.

Normally energized: the output is normally

PQTSoft Remote

Configuration

Digital output connections

29

47

27

PQTSoft Remote

26

Configuration

8

4

2

3

1

5

6

energized and it’s de-energized in case of alarm.
Normally de-energized: the output is normally de-ener-
gized and it’s energized in case of alarm.

Analogue output alarm setup

Where “BO...” shows the module and output to which the
window refers. Analogue outputs are referred to as follows:
A0 OUTPUT: analogue output 1, SLOT A
A1 OUTPUT: analogue output 2, SLOT A
B0 OUTPUT: analogue output 3, SLOT B
B1 OUTPUT: analogue output 4, SLOT B
[1] Selects the variable to be retransmitted: click the
pointer of the “Variable” drop-down menu. Click the
pointer of the “Scale and decimal point position
drop-down menu to select the scale and decimal point.
[2] Max input value”: selects the max. value of the variable
input range. “Min. input value”: selects the min value of the
variable input range. [3] Max output value”: value expressed
as % of the full scale value (0-20mA, 0-10V, etc.) that is gen-

1

2

3