Manual_G0-GB-GXP5-GXU5_406_EN.docx

27/48

Baumer IVO GmbH & Co. KG

20.11.12

Villingen-Schwenningen, Germany

Object 1011

Restore parameters

The values in the RAM are overwritten by the default values (see object 1010h) by the object 1011h. In
addition, the content of the EEPROM is marked as invalid. This means that until the next data save
routine in the EEPROM, the default values are loaded in each case.
In order to prevent unintentional overwriting, the message "load" must be written in subindex 1.

COB ID

DLC Command

Object L

Object H Subindex

Data 0

Data
1

Data
2

Data
3

600h+node ID

8

23h

11h

10h

01

6Ch 'l'

6Fh
'o'

61h 'a' 64h 'd'

Object 1014

COB ID emergency message

Subindex

0

Data type

Unsigned 32

Access

Read write

Default

80h+node ID

EEPROM

Yes

Description

Defines COB ID of the emergency object

Values

80h + Node ID

Object 1016

Consumer heartbeat time

Subindex

0

Data type

Unsigned 8

Access

Read only

Default

1

EEPROM

No

Description

Biggest supported subindex

Values

1 = Biggest supported subindex


Subindex

1

Data type

Unsigned 32

Access

Read write

Default

10000h

EEPROM

Yes

Description

Consumer heartbeat time

Values

Bit 0..15 Consumer heartbeat time in ms
Bit 16..23 Node ID

Object 1017

Producer heartbeat time

Subindex

0

Data type

Unsigned 16

Access

Read write

Default

0h

EEPROM

Yes

Description

Defines repeat time of the heartbeat watchdog service

Values

0 = Disabled
1..65535 = Repeat time in ms