SDO abort message
If SDO communication is not running smoothly, an abort code is transmitted as the SDO response:

05040001h

: Command byte is not supported

06010000h

: Incorrect access to an object

06010001h

: Read access to write only

06010002h

: Write access to read only

06020000h

: Object is not supported

06090011h

: Subindex is not supported

06090030h

: Value outside limits

06090031h

: Value too great

08000000h

: General error

08000020h

: Incorrect save signature ("save")


4.3. Useful information relating to the sensor

Resetting the node ID

1. The node ID is reset using the Baumer IVO specific object 2101h.
2. After setting the node ID, this must be saved in the EEPROM with object 1010h.
3. On next initialization, the sensor logs on with the new node ID.

Resetting the baud rate

1. The baud rate is reset with the Baumer IVO specific object 2100h.
2. After setting the baud rate this must be saved in the EEPROM with object 1010h.
3. On next initialization, the sensor logs on with the new baud rate.
4. ! DO NOT FORGET TO SET THE MASTER TO THE NEW BAUD RATE !

Shielding
As the encoder is not always connected to a defined earth potential depending on its mounting position, the
encoder flange should always be additionally linked to earth potential. The encoder should always on
principle be connected to a shielded conductor.
If possible the cable shield should be in place at both ends. Ensure that no equalizing currents are
discharged via the encoder.