3 ac power wiring, 4 battery option, 4 cable connections and installation – Rice Lake Intrinsically Safe User Manual

Page 16: Ac power wiring, Battery option

Advertising
background image

10

320IS Installation Manual

A separate conduit system is recommended for installation. The type suggested for this application is 3/4" rigid

steel conduit with pull boxes located at required intervals. The conduit provides additional noise protection for the

low-level signals, while automatically complying with the requirements for two-inch separation between

intrinsically safe circuits and other electrical cables. Conduit seals are necessary where a gas tight seal is required

between hazardous area and safe area.

2.3.3

AC Power Wiring

Standard units are powered by an F.M. approved power supply. We recommend the 100–240 VAC into RLWS

IS-EPS-100-240 Intrinsically safe DC output power supply (PN 72713).
See the IS-EPS-100-240 Power Supply Instruction Sheet (PN 79820) for information on wiring and power

specifications.

2.3.4

Battery Option

The optional battery pack provides an intrinsically safe battery that can replace the power supply. The battery is

approved for use in hazardous environments and limited use operations such as bench scales and platform scales. A

low battery error message will display to indicate that the battery needs to be recharged. Always charge the battery

overnight. The yellow indicator light will remain on until the battery is charged at about 70%, at which point the

indicator light will turn green and the charger will switch to float charge mode. Once the light turns green, the

battery requires another 3 hours on float charge before the battery is fully charged.

To keep battery at full capacity, it is recommended to leave the battery connected to the charger, in float
charge mode, until ready to use. The battery can remain on the charger in float charge mode indefinitely
without damaging the battery. See Battery Charging Instruction Sheet (PN 96567) for instructions on charging
the battery.

While connected to the DC battery pack with the indicator off, the 320IS still draws a small amount of current
that will shorten battery run time. To preserve battery life, disconnect the battery when not in use.

2.4

Cable Connections and Installation

The following sections contain information on cable connections and installation for the

320IS

.

Intrinsically safe cables are specified by control drawing. All cables must have appropriate internal inductance
and capacitance. Cable lengths are based on group classifications.

Figure 2-2. Metal Cord Grip

Load Cell Size

Quantity of cells

Operating Time

350

 load cell

1

40 - 50 hours

4

35 - 40 hours

700

 load cell

1

45 - 55 hours

4

40 - 50 hours

Table 2-2. Estimated Battery Operating Times

Note

Note

Note

Advertising
This manual is related to the following products: