Operation principle, Compur statox 4120 – Compur STATOX 4120 User Manual

Page 6

Advertising
background image

Compur Statox 4120





pic. 2: Statox 4120 sensor head for Cl

2

und ClO

2

Operation principle

Ambient air enters the sensor (2) by diffusion through an opening at the bottom. The sensor creates a
current - signal proportional to the gas concentration. This signal is amplified, temperature
compensated and linearised. As a digital signal it is transmitted to the control module.

To protect the sensor from being poisoned by a high gas concentration, the Statox features a built – in
air purge. This is activated when the gas concentration exceeds 95 % of the measuring range and
stops when it has dropped below 80 %.

The battery pack (7) buffers the energy demand of the built – in pump (5). It is on permanent trickle
charge. The pump is activated in the protection mode and during the self test to purge the sensor and
provide test gas from the gas generator (4) to the sensor.

2.2 Statox 4120 rack


The Statox 4120 rack and the Statox 4120 control module provide the power supply for the sensor
head. They are certified explosion proof [EEx ib] IIC. The rack must not be installed in certified
areas!




6