Load cell wiring diagrams, Hi 1756 1df valve wiring diagram – Hardy HI 1756-nDF User Manual

Page 13

Advertising
background image


9

Chapter 3

Check to be sure that the connector is completely
plugged in before operating the module.

NOTE

Most module-related problems are due to loose
connections. Be sure to check the I/O connection first
in the event you have a problem receiving
information from the load cells or if the relays do not
operate correctly.

Single Channel

Pin 1 Exc+
Pin 2 Sense+
Pin 3 Sig+
Pin 4 Sig-
Pin 5 Sense-
Pin 6 Exc-
Pin 7 C2+
Pin 8 C2-
Pin 9 Shield

Load Cell Wiring Diagrams

The diagrams below show how Hardy Load Sensor with C2 wiring differs from standard
Load Cell wiring. C2 wiring is required when using a Integrated Technician summing
junction box. The C2 wires are used fro communicating IT and C2 commands.

Industry standard load cells wiring

Hardy load sensor/c2 wiring

HI 1756 1DF Valve wiring diagram

+Exc

-Exc

+Sen

+Sig

-Sig

-Sen

+C2

-C2

Shield

RA1 IP

RA1 OP

RA1 COM

RB1 IP

RB1 OP

RB1 COM

1756-1DF

C2

Shield

Load Cell

(0-24Vdc, 3.5A)

Valve

1

(0-24Vdc, 3.5A)

Valve

2

Control Voltage 2

Control Voltage 1

COM2

COM1