Chapter 4

The flow rate is affected by the composition of the material, for example liquids will
provide a linear flow rate as they are dispensed compared to “lumpy” material which due
to product binding and asymmetric shape will cause short term disturbances in the weigh
reading and subsequent flow rate calculations.

To provide a reliable flow rate reading with a range of materials the following four flows
rate filters are provided, see the “flow Rate Filter” parameter in the table below.

Parameters for configuring the flow rate calculation are detailed in the following tables:

DINT Configuration Parameters used in Flow Rate Control

Parameter

Default

Description

Weight Unit

3

Weight unit selection

Value

Frequency (Hz)

0

Pounds(lb)

1

Ounces(oz)

2

Ton(ton) short ton

3

Kilograms(kg)

4

Grams(g)

5

Metric Tonnes (t) long ton

Flow Rate
Period

0

Flow Rate options

Ref#

FR unit of time

0

seconds

1

minutes

2

hours

Weight Filter 2

The weigh scale data used in the weight calculation can
be derived from one of three filters. The selection is
based on a compromise between the response time
required and the inherent noise within the measured
value.

FILT

Function

0

Raw ADC data samples

1

Low Pass filter

2

Waversaver output data

Material

0

The material texture can cause fluctuations in the
instantaneous weight readings. To compensate for these
periodic fluctuations set to 0 for liquids and fine
materials and 1 for coarse materials.