Overview of operation, Overview of weight calculation – Hardy HI 1756-nDF User Manual

Page 20

Advertising
background image


16

Chapter 4

Overview of Operation

The HI 1756 nDF will calculate Gross weight, Net weight, & Flow Rate (FR) outputs
simultaneously, as shown in the simplified block diagram below.

Weigh Filter
NumAVg

Weight

Conditioning

Weight

Calculation

Weight
Value

Flow Rate

Calculation

Flow Rate Time Base

Weight Unit

Flow Rate

Filter

Flow Rate
Value

Load Cell

Signal

Flow Rate Update Period
Flow Rate Filter
Material

ADC

Weight Update Rate

Current
Flow Rate

Auto_Preact

Calculation

Auto_Preact

stable
capture time

p gain
i gain
frc tolerance

variation
capture
steady period

auto preact config
start wait
fast adjust

Simplified block diagram for the 1756-1DF

Overview of Weight Calculation

The ADC data can be filtered to reduce short term disturbances caused by system noise,
vibration noise, and local short term disturbances that could affect the weigh
measurement.

The most robust method to reduce these system disturbances is Waversaver®, but this
mode has the longest delay which is directly proportional to the bandwidth selected as the
algorithm requires at least one full cycle of the lowest frequency to be able to remove the
noise and harmonics from the weight measurement. On the other hand the raw data
sample mode provides the fastest response with no additional delay but does not filter out
any noise from the sampled data. As a compromise a low pass filter can be selected to
provide noise shaping across multiple samples centered on the current weigh value; this
mode has a fixed delay of 100mS.

The filter selection will depend upon the environment and the desired response time to
changes in weight.