Hardy HI 1756-nDF User Manual

Page 19

Advertising
background image


15

Chapter 4

Linking the PLC with the HI 1756-nDF Dispenser Filler Control
Module

To set parameters for the weigh scale module, you must establish communications with a
ControlLogix PLC. Follow the steps below to set up the communication link without
using the AOP. You will need a new or open RS Logix® 5000 project. For instructions,
see your RS LOGIX 5000 manual.

Step 1. Look for a list of folders on the left side of the screen. Scroll to and select the

I/O Config folder, which will open a menu.

Step 2. Select New Module to display a list of modules.

Step 3. Select the Generic 1756 module to open the Module Properties form.

Step 4. Enter the following connection parameters in the appropriate fields:

Name of Module

Description of Module (Optional)

Slot ID

Input Assembly Instance:101 Size = 16

Output Assembly Instance: 100 Size = 16

Configuration Assembly Instance: 102 Size = 200 for a single channel

(1756 1DF) or 400 for a dual channel (1756 2DF)

Step 5. Select DATA REAL from the Comm Format pull-down list.

Step 6. Open the Connection Tab.

Step 7. Set the RPI to 5 milliseconds or greater Do not set this parameter lower than 5

milliseconds.

Step 8. Click Finish.