Chapter 4

command

Number

description

SETRELAY**

7.0

Default setting is 0, both relays OPEN
Manual mode for testing relay operation.
0 = both relays RB and RA are OPEN
1 = relay RB is OPEN, and relay RA is CLOSED
2 = relay RB is CLOSED, and relay RA is OPEN
3 = both relays RB and RA are CLOSED
The manual relay setting can be overridden by the
STARTANDTARE and the STARTNOTARE commands.

WARNING: Forcing the relay may cause damage or
personal injury. Make absolutely sure that you know
what the relay is connected to before activating.


** Repeatable Command

RELOADNV

16.0

Reload Non-Volatile
Recall all parameters from non volatile memory.

WRITENNV

17.0

Write Non-Volatile
Save all parameters to non volatile memory.

STARTREFILL

18.0

Starts a manual refill cycle

TARECMD

98.0

TARE: zero the net weight

ZEROCMD

99.0

Zero the gross weight

CALLOWCMD

100.0

Hard calibration, low step.

CALHIGHCMD

101.0

Hard calibration, high step.

C2CALCMD

102.0

C2 calibration.

WRITEPARAM

103.0

Write a single parameter.
To write a single parameter, send the command 103.0.
Specify the parameter to be changed by putting the
parameter number in float number 1, and put the new
parameter value in float number 2 of the output table.

READPARAM**

105.0

Read a single parameter.
To read a single parameter, send the command 105.0.
Specify the parameter to read by putting the parameter
number in float number 1.
The parameter value will appear in word 2 of the input
table.
** Repeatable Command

RESETFR

112.0

Clear all old data from the flow rate (FR) weight buffer.
This has the effect of zeroing the flow rate value.

RESETAPCMD

113.0

Reset Auto Preact Command
Resets all stored values in the auto preact function to their
factory default values.

SETDEFAULT

148.0

Replaces all parameter values with the factory default
parameters values.