IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A

Chapter 7. SLC/PLC-5/MicroLogix Interface - 105

PLC-5 and SLC Messages

PLC-5 Programmable Controllers System Selection Guide, Rockwell Publication 1785-SG001A-EN-P

Ethernet Interface Module Series B, Revision D Product Release Notes, Rockwell Publication 1785-
RN191E-EN-P

Note: Older versions of firmware may or may not provide Ethernet/IP functionality.

7.3. PLC-5 and SLC Messages

The following PCCC messages are supported for the PLC-5 and SLC 5/05 PLCs.

The Receive Port Information is provided in one continuous file. The following file addresses are used to
retrieve the various parameters.

Message Type

PCCC Message ID

Maximum Message Size

Maximum Serial Packet Size

SLC Typed
Read

162

CLX: 242 SINTs (121 INTs)
SLC: 206 SINTs (103 INTs)
PLC-5: 240 SINTs (120
INTs)

CLX: 238 SINTs (119 INTs)
SLC: 202 SINTs (101 INTs)
PLC-5: 236 SINTs (118 INTs)

SLC Typed
Write

170

CLX: 220 SINTs (110 INTs)
SLC: 206 SINTs (103 INTs)
PLC-5: 238 SINTs (119
INTs)

216 SINTs (108 INTs)
SLC: 202 SINTs (101 INTs)
PLC-5: 234 SINTs (117 INTs)

PLC-5 Typed
Read

104

CLX: 234 SINTs (117 INTs)
SLC: 252 SINTs (126 INTs)
PLC-5: 238 SINTs (119
INTs)

230 SINTs (115 INTs)
SLC: 248 SINTs (124 INTs)
PLC-5: 234 SINTs (117 INTs)

PLC-5 Typed
Write

103

CLX: 226 SINTs (113 INTs)
SLC: 226 SINTs (113 INTs)
PLC-5: 224 SINTs (112
INTs)

CLX: 222 SINTs (111 INTs)
SLC: 222 SINTs (111 INTs)
PLC-5: 220 SINTs (110 INTs)

IO-Link

Port 1

IO-Link

Port 2

IO-Link

Port 3

IO-Link

Port 4

Access

Length

PDI Data Block

N10:0

N20:0

N30:0

N40:0

Read-Only

Configurable per port

Note: See the table

below for details.

Receive PDO
Data Block

N11:0

N21:0

N31:0

N41:0

Read-Only

Configurable per port

Note: See the table

below for details.

Transmit PDO
Data Block

N12:0

N22:0

N32:0

N42:0

Write-
Only

Configurable per port

Note: See the table

below for details.

Receive ISDU
Response

N13:0

N23:0

N33:0

N43:0

Read-Only

4 INTs to Max Msg Size

Transmit ISDU
Request

N14:0

N24:0

N34:0

N44:0

Write-
Only

4 INTs to Max Msg Size

Port Information Block (Continuous Block)

464 Bytes
(232 INTs)