Comtrol IO-Link Master EIP-4 User Manual

Page 69

Advertising
background image

IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A

Chapter 4. IO-Link Port Configuration - 69

EtherNet/IP Settings Parameters

PDO Data Byte-Swap Method

Default: Word (16-bit) byte-swap

If enabled, the IO-Link Master swaps the data bytes in word (2 byte)
format or dword (4 byte) format. Supported values are:

No byte-swap – data passed through as received

Word (16-bit) byte-swap – data is byte-swapped in word format

Dword (32-bit) byte-swap – data is byte-swapped in dword format

Note: The byte swapping must be set correctly in order to convert from

EtherNet/IP (little-endian byte order), to IO-Link (big-endian byte
order).

Clear Event Code in PDO Block

Default: False

If enabled, the IO-Link Master expects the first 2 bytes, word, or dword of
the PDO block to be used for event code handling. Supported values are:

True = expect event code

False = no event code, expect only PDO data

Clear Event Code After Hold
Time

Default: True

If enabled, the IO-Link Master clears any event code reported in the PDI
data block after the Event Active Hold Time. Supported values are:

True = clear event code after hold time

False = do not clear event code after hold time

Event Active Hold Time

Default: 1000 ms

If Clear Event Code After Hold time is enabled, the time period an event
code is reported in the PDI block before it is cleared.

Valid range: 1-65535

Valid Units:

-

ms (milliseconds)

-

sec (seconds)

-

min (minutes)

-

hours

-

days

Clear Event Hold Time

Default: 500 ms

Once an event code has been cleared, the time an event code stays cleared
in the PDI block before another event code can be reported.

Valid range: 1-65535

Valid Units:

-

ms (milliseconds)

-

sec (seconds)

-

min (minutes)

-

hours

-

days

EtherNet/IP Settings Page (Continued)

Advertising