IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A

Chapter 3. EtherNet/IP CIP Object Definitions - 43

ISDU Read/Write Object Definition (74 hex)

All PDO data is received and returned in the configured PDO format (8-bit, 16-bit or 32-bit). Refer to

3.3. PDO

(Process Data Output) Transfer Object Definition (73 hex)

on Page 42 for a detailed explanation of the PDO

data block.

3.4. ISDU Read/Write Object Definition (74 hex)

The ISDU Read/Write object defines the attributes by which the PLC can:

Send an ISDU request containing one or more read and/or write ISDU commands to an IO-Link device
via the IO-Link Master.

Request the ISDU response(s) from the IO-Link Master.

Send both blocking and non-blocking ISDU requests.

Refer to the ISDU Handling chapter for a detailed description of the ISDU functionality.

3.4.1. Class Attributes

The following table shows the Class Attributes for the ISDU Read/Write Object Definition (74 hex).

3.4.2. Instance Attributes

The following table shows the Instance Attributes for the ISDU Read/Write Object Definition (74 hex).

3.4.3. Common Services

The following table shows the Common Services for the ISDU Read/Write Object Definition (74 hex).

Attribute ID

Name

Data Type

Data Value(s)

Access Rule

1

Revision

UINT

1

Get

2

Max Instance

UINT

4

Get

3

Num Instances

UINT

4

Note: Instance number determines IO-

Link port on the IO-Link Master.

Get

Attribute ID

Name

Data Type

Data Value(s) Access Rule

1

ISDU Response

ISDU response data block

0-255

Get

2

ISDU Read/Write Request

ISDU request data block

0-255

Set

Service Code Implemented in Class

Implemented in Instance

Service Name

01 hex

Yes

No

Get_Attributes_All

0E hex

Yes

Yes

Get_Attribute_Single

10 hex

No

Yes

Set_Attribute_Single

02 hex

No

No

Set_Attribute_All