Status word, Common services, Status word 3.5.4. common services – Comtrol IO-Link Master EIP-4 User Manual

Page 46

Advertising
background image

46 -

Chapter 3. EtherNet/IP CIP Object Definitions

IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A

Status Word

3.5.3. Status Word

Refer to Page 52 of Volume 3.5 of the CIP Common Specification.

The following applies to the Identity Object status word for the IO-Link Master.

3.5.4. Common Services

Status Word Bit

Setting

Description

0

0

Ownership Flag. Does not apply to the IO-Link Master.

1

0

Reserved.

2

0

IO-Link Master is operating on the default configuration.

1

The IO-Link Master has a configuration other than the default
configuration.

3

0

Reserved.

4-7

0101 (0x50) Indicates that there is a major fault (either Bit 10 or Bit 11 is set).

0100 (0x40) Indicates the stored configuration is invalid.

0011 (0x30)

Indicates the system is operational and there are no I/O (Class 1)
connections.

0110 (0x60)

Indicates the system is operational and there is at least one active
I/O (Class 1) connection.

0000

Indicates the system is not operational. It may be in any of the
following states:

System startup.

Configuration in process.

Idle.

Critical (major) fault.

8

0

No recoverable minor fault. No error history entry reported within
the last ten seconds.

1

Recoverable minor fault. The IO-Link Master has reported an
error within the last ten seconds and a major fault has not been
detected.

9

1

Unrecoverable minor fault. Does not apply to the IO-Link Master.

10

0

No recoverable major fault.

1

A major recoverable fault exists. This is a fault that the IO-Link
Master may be able to recover from by a system reset. If the
system does not recover automatically, a system reset message or a
power cycle of the IO-Link Master may be required.

11

0

No major unrecoverable fault.

1

A major unrecoverable fault has occurred in the IO-Link Master. If
the major fault is not corrected with a system reset or a power
cycle, refer to the User Manual or call Comtrol support.

12-15

0

Reserved.

Service Code Implemented in Class

Implemented in Instance

Service Name

01 hex

Yes

Yes

Get_Attribute_All

Advertising