3 locating vent and combustion airterminals – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 16

Advertising
background image

Page 12

LAARS Heating Systems

NeoTherm and shown in the Unpacking section, be installed.

Be sure to install and terminate both vent and combustion

air pipes per the Venting and Combustion Air section of the

NeoTherm instructions.

3.3 Locating Vent and Combustion Air

Terminals

Side Wall Vent Terminal
The appropriate Laars side wall vent terminal must be used.

The terminal must be located in accordance with ANSI

Z223.1/NFPA 54 and applicable local codes. In Canada, the

installation must be in accordance with CSA B149.1 or .2

and local applicable codes. Consider the points listed on the

following page when installing the terminal.
1.

Figure 12 shows the requirements for mechanical vent

terminal clearances for the U.S. and Canada.

2.

Vent terminals for condensing appliances or appliances

with condensing vents are not permitted to terminate

above a public walkway, or over an area where

condensate or vapor could create a nuisance or hazard.

3.

Locate the vent terminal so that vent gases cannot be

drawn into air conditioning system inlets.

4.

Locate the vent terminal so that vent gases cannot enter

the building through doors, windows, gravity inlets or

other openings. Whenever possible, avoid locations

under windows or near doors.

5.

Locate the vent terminal so that it cannot be blocked

by snow. The installer may determine that a vent

terminal must be higher than the minimum shown in

codes, depending upon local conditions.

6.

Locate the terminal so the vent exhaust does not settle

on building surfaces or other nearby objects. Vent

products may damage surfaces or objects.

7.

If the boiler or water heater uses ducted combustion air

from an intake terminal located on the same wall, see

Figures 12-14 for proper spacing and orientation.

If the vent termination is located in an area exposed to high

winds, an optional PVC tee (the same diameter as the vent

pipe) may be used. The tee’d vent termination offers greater

protection from wind related operating issues.

Side Wall Combustion Air Terminal
The LAARS side wall combustion air terminal, or concentric

terminal must be used when the heater takes air from a side

wall. (See Table 3.) Contact Laars for AL29-4C termination

fittings. Consider the following when installing the terminal.

(See Figures 12-14.)
1.

Do not locate the air inlet terminal near a source of

corrosive chemical fumes (e.g., cleaning fluid, chlorine

compounds, etc.)

2.

Locate the terminal so that it will not be subject to

damage by accident or vandalism. It must be at least 7

feet (2.1m) above a public walkway.

3.

Locate the combustion air terminal so that it cannot be

blocked by snow. The National Fuel Gas Code requires

that it be at least 12 inches (30cm) above grade, but the

installer may determine it should be higher, depending

upon local conditions.

4.

If the NeoTherm is side-wall vented to the same wall,

locate the vent terminal at least 1 foot (0.3m) above the

combustion air terminal.

5.

For concentric vent, follow instructions included

with vent kit.

6.

Multiple vent kits should be installed such that the

horizontal distance between the outlet group and the

inlet group is 36” (90cm). (See Figure 13.)

7.

The vent outlet for models 80-285 must be no lower

than the center of the air inlet, and must be at least 12”

(30cm) away from the air inlet. Vent outlets for models

399-850 must be at least 12” above the top of the air

inlet, and must be at least 36” (90cm) horizontally from

the air inlet. (See Figure 14.)

Vertical Vent Terminal
When the unit is vented through the roof, the vent must extend

at least 3 feet (0.9m) above the point at which it penetrates

the roof. It must extend at least 2 feet (0.6m) higher than

any portion of a building within a horizontal distance of 10

feet (3.0m), and high enough above the roof line to prevent

blockage from snow. The vent terminal included with the

NeoTherm can be used in both vertical and horizontal

applications. When the combustion air is taken from the roof,

the combustion air must terminate at least 12” (30cm) below

the vent terminal. (See Figure 10.)

Vertical Combustion Air Terminal
When combustion air is taken from the roof, a field-supplied

rain cap or an elbow arrangement must be used to prevent

entry of rain water. (See Figure 10.) The opening on the end

of the terminal must be at least 12” (30cm) above the point at

which it penetrates the roof, and high enough above the roof

line to prevent blockage from snow. When the vent terminates

on the roof, the combustion air must terminate at least 12”

(30cm) below the vent terminal.

Installations in the Commonwealth of

Massachusetts
In Massachusetts the following items are required if the

side-wall exhaust vent termination is less than seven (7) feet

above finished grade in the area of the venting, including but

not limited to decks and porches. From Massachusetts Rules

and regulations 248 CMR 5.08 (begininning on 2nd page

following):

Advertising
This manual is related to the following products: