6b.3 cold water make-up, 6a.4 condensate drain, 6b.5 freeze protection – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 31: 6b.6 ntv suggested piping schematics, 6b.7 ntv suggested pumps

Advertising
background image

Page 27

N

eo

T

herm

Boilers and Water heaters

6B.3 Cold Water Make-Up

The cold water make-up may be connected to the tank or to

the inlet of the boiler as shown in Figures 22-25

.

Install back

flow preventers and shut offs where needed or required by

code. Pipe sizes may have to be increased to accomodate cold

water make-up flow.

6A.4 Condensate Drain

A condensate drain trap is built into the NeoTherm unit.
Connect a 3/4” PVC pipe between the drain connection and

a floor drain (or a condensate pump if a floor drain is not

accessible).
The condensate drain must be installed so as to prevent

accumulation of condensate. When a condensate pump is not

used, the tubing must continuously slope downward toward

the drain with no spiraling.
Consult local codes for the proper disposal method for the

condensate.

Caution

Condensate is mildly acidic (pH = 5), and may harm

some floor drains and/or pipes, particularly those

that are metal. Ensure that the drain, drainpipe,

and anything that will come in contact with the

condensate can withstand the acidity, or neutralize

the condensate before disposal.

Damage caused by

failure to install a neutralizer kit or to adequately

treat condensate will not be the manufacturer’s

responsibility.

6B.5 Freeze Protection

NeoTherm heaters are not certified for outdoor installation,

so the chance of freezing is minimized. In an event such as

power outage, component failure or other issue when freezing

is likely, the heater and system must be drained to avoid the

risk of damage due to freezing. Glycol must not be used in

volume water heating applications.

6B.6 NTV Suggested Piping Schematics

Figures 23-25 show suggested piping configurations for

NTV boilers. These diagrams are only meant as guides.

All components or piping required by local code must be

installed.

6B.7 NTV Suggested Pumps

Possible pumps for NTV sizes 600-850 are Grundfos

model TP 40-160/2B, or for size 600 (only) is Armstrong

model E22B. See Table 8 for heater water flow and head

requirements.
Note - The head loss for the piping, fittings, and accessories

must be calculated and added to the heater head loss to get the

total required pump head. An undersized pump will result in

insufficient flow. The can result in scale buildup and failure

of the heat exchanger.

Advertising
This manual is related to the following products: