Tables - propane/nat gas conversion kits – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 61

Advertising
background image

Page 57

N

eo

T

herm

Boilers and Water heaters

NT size (mbtu)

Kit number

80 CA006201
105 CA006202
150 CA006203
199 CA006204
210 CA006204
285 CA006205
399 CA008600
500 CA008600
600 CA008600
750 CA008600
850 CA008600

Table 16a - Propane Gas Conversion Kits

NT size (mbtu)

Kit number

80 CA006206
105 CA006206
150 CA006206
199 CA006206
210 CA006206
285 CA006206
399 CA008600
500 CA008600
600 CA008600
750 CA008600
850 CA008600

Table 16b - Natural Gas Conversion Kits

12. Place the appliance in operation according to the

instructions in Section 10. Check all gas connections for

leaks. Confirm that all fasteners are tight.

Optional Gas Pressure Switches
The high and low gas pressure switches are 24V manual reset

switches that act to cut power to the gas valves if the gas

pressure is too low or too high for proper operation. The gas

pressure switches used are integrally vent limited, and do not

require venting to atmosphere. To remove a switch, remove

the screw on the plastic housing and pull the clear cover off.

Disconnect the two wires from the screw terminals. Twist

the switch off the pipe nipple. Reassemble in reverse order.

For natural gas, set the low gas pressure switch to 3” w.c. For

propane, set the low gas pressure switch to 5” w.c. For natural

and propane, set the high gas pressure switch to 14”.

10.3 Gas Conversion

NeoTherm units can easily be converted from natural to

propane gas or from propane to natural gas in the field. Some

units require the addition of a gas orifice along with proper

gas valve adjustment. Other units require no additional parts

- only proper gas valve adjustment. Please contact the Laars

factory for specific information regarding the gas conversion

of a particular appliance. If a gas conversion is performed,

the unit must be identified with the appropriate gas labels

and a conversion sticker to allow technicians performing

maintenance in the future to properly identify the type of gas

being used in the appliance.