Minimum venting distance – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 18

Advertising
background image

Page 14

LAARS Heating Systems

1. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall vented gas

fueled appliance, the installing plumber or gas-fitter shall

observe that a hard-wired carbon monoxide detector with

an alarm battery back-up is installed on the floor level

where the gas appliance is to be installed. In addition, the

installing plumber or gasfitter shall observe that a battery

operated or hard-wired carbon monoxide detector with an

alarm is installed on each additional level of the dwelling,

building or structure served by the side-wall horizontally

vented gas fueled equipment. It shall be the responsibility

of the property owner to secure the services of quali-

fied licensed professionals for installation of hard-wired

carbon monoxide detectors.

a. In the event that the side-wall horizontally vented gas

fueled equipment is installed in a crawl space or an attic,

the hard-wired carbon monoxide with alarm and battery

back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of the subdivision

cannot be met at the time of completion of installa-

tion, the owner shall have a period of thirty (30) days to

comply with the above requirements, provided, however,

that during said thirty (30) day period, a battery operated

carbon monoxide detector with an alarm be installed.

2. Approved Carbon Monoxide Detectors

Each carbon monoxide detector shall comply with NFPA

720 and be ANSI/UL 2034 listed and IAS certified.

3. Signage

A metal or plastic identification plate shall be permanent-

ly mounted to the exterior of the building at a minimum

height of eight (8) feet above grade directly in line with

the exhaust vent terminal for horizontally vented gas fu-

eled heating appliance or equipment. The sign shall read,

in print no less than one-half (1/2) inch in size: “GAS

VENT DIRECTLY BELOW, KEEP CLEAR OF ALL

OBSTRUCTIONS.”

4. Inspection

The state or local gas inspector of the side-wall hori-

zontally vented gas fueled appliance shall not approve

the installation unless, upon inspection, the inspector

observes carbon monoxide detectors and signage installed

in accordance with the provisions of 248 CMR 5.08(2)

(a) 1-4.

Figure 14 - Minimum Venting Distance

Figure 13 - Multiple Side-Wall Terminals,

Air and Vent

Advertising
This manual is related to the following products: