LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 45

Advertising
background image

Page 41

N

eo

T

herm

Boilers and Water heaters

DHW Temperature Setting -
Regardless of the type of DHW setup, the setpoint adjustment

is made the same way.

How to get there: From the “Home” screen, press “I” to

go to “Info/ Install.” Choose “Advanced Setup,” then go

to “DHW Setpoint.”

Hydronic Heating with

Domestic Hot Water (DHW) Priority -
When using the NeoTherm for hydronic heating with

domestic hot water priority, a call for heat must be supplied

to the “T-T or Interlock” terminal. Once the call is supplied,

the control starts the Boiler and System pumps and begins the

ignition process. Once in Run, the NeoTherm monitors the

flame signal, call for heat, safeties, and water temperatures

modulating as needed between 100% and 20% of rate to

satisfy the call for heat. When a DHW demand is applied

during a hydronic call for heat, the priority feature forces the

boiler to switch to the DHW demand for the priority time.

The DHW priority demand forces the control to operate to the

DHW setpoint, de-energizes the System pump and energizes

the DHW pump.
The domestic hot water temperature sensor or an aquastat

is used to monitor the DHW demand. The control uses the

DHW sensor to control the operation and modulation rate of

the appliance when there is a DHW demand.

Domestic Hot Water Demand - NTV only -
The “NTV” NeoTherm units are designed to provide “volume

water” DHW in conjunction with a storage tank. When the

NTV model NeoTherm is used in this application, a call for

heat must be supplied to the “DHW stat” terminal located on

terminal block 6 (TB6). The DHW heating call can be from

the supplied DHW sensor or from an aquastat. If the DHW

sensor is used, the heater operates to maintain the temperature

at the DHW sensor. (This may allow the actual heater outlet

water temperature to exceed the DHW sensor setpoint.) If

an aquastat is used to supply the DHW demand, the heater’s

firing rate is controlled by the DHW setpoint temperature and

the water temperature at the heat exchanger outlet.
When the unit receives the DHW call, the control starts the

Boiler and DHW pumps and begins the ignition process. Once

in Run, the NeoTherm monitors the flame signal, call for

heat, safeties, and water temperatures modulating as needed

between 100% and 20% of rate to satisfy the call for heat.

Hydronic Heating Using Local Lead-Lag/Cascading

Feature with Indirect Hot Water -
(For a complete explanation of the Lead/Lag system, see

Section 8C.8.)
When using the Lead/Lag boiler system to provide indirect

domestic hot water heating, the DHW demand should be

supplied to the Master boiler through the existing DHW

terminals. The Lead/Lag system will change the operating

mode of just the Master boiler to supply water at the DHW

setpoint. The remaining boilers on the system will continue to

supply hydronic heating.
When the system is supplying both hydronic heat and

domestic hot water at the same time, both the System pump

and DHW pump contacts are closed, so special attention must

be paid to allow for proper operation. In applications serving

both hydronic and domestic heating, during a DHW call the

Boiler pump on the Master boiler may need to be turned

off. The DHW pump will provide flow through the boiler

and indirect tank when there is a DHW call. (This means the

DHW pump must be sized properly.) To turn off the boiler

pump in this application, the “boiler pump interrupt” jumper

must be installed. The terminal block location is terminal

block 5 (TB5) at the contacts labeled “boiler pump interrupt”

in the control panel.

Sensor Connection for Domestic Hot Water -
Connect the DHW sensor or aquastat.

If your system has just one boiler –
Connect the sensor across terminals 5 and 6 on TB6.
If your system has more than one boiler, and is controlled

using the Lead/ Lag function –
On the unit used as the Lead/ Lag Master only, connect the

sensor across terminals 5 and 6 on TB6.

Domestic Hot Water Heating

Using External Modulation Control -
When the NeoTherm is used for DHW heating with external

modulation control, a call for heat must be supplied to the

“T-T or Interlock” terminal. By supplying a call to the “T-T

or interlock” terminal, the operating temperature setpoint

defaults to the hydronic heating setpoint, so all of the tem-

perature adjustments must be made to the hydronic setpoint.

When the unit receives the call, the control starts the Boiler

and System pumps and begins the ignition process. Once in

Run, the NeoTherm monitors the flame signal, call for heat,

safeties, and water temperatures. The heater setpoint is used

to limit the maximum water temperature leaving the boiler

only. The modulation rate is controlled by a 4-20mA signal

supplied by an external control. (This can also be 0-10Vdc us-

ing a converter.) When setting up a system using an external

control, take care to set Anti-Short Cycle feature to prevent

“hunting “ and possible premature component failure.