Section 8A -

QUICK START MENU

Section 8 is divided into three parts. Section 8A includes instructions for using the Quick Start

menu. Section 8B covers basic installation and wiring. Section 8c includes more detailed setup

instructions and wiring diagrams.

Fig. 35 - Quick Start Menu

.
Changing the CH (Central Heat) Setpoint -

Fig. 36 - Changing the CH Setpoint

• On the Quick Start menu, use the Up- and Down-Arrows

to go to the line for CH Setpoint. Press the large OK

button to select the line.

• Use the Up- and Down-Arrow buttons to select the value

you want.

• Press the round OK button to enter the new value.

Changing the DHW (Domestic Hot Water) Setpoint -
See the procedure described above for the CH setpoint.

Outdoor Reset Functions -
The next four lines in the display are used to set up the

Outdoor Reset functions:
• Outdoor Reset Enable/Disable - Note: This function can

be Enabled/Disabled only by a factory trained technician.

• Low Water Temperature - Use the Up- and Down-Buttons

to select the function, use Up- and Down- to select the

new value, then press the round OK button.

• Maximum Outdoor Temperature - Use the Up- and Down-

Buttons to select the function, use Up- and Down- to

select the new value, then press the round OK button.

• Minimum Outdoor Temperature - Use the Up- and Down-

Buttons to select the function, use Up- and Down- to

select the new value, then press the round OK button.

For a complete explanation of the setup for Outdoor Reset,

see Section 8C.5.

Adjustable High Limit -
The absolute high limit setting for the water outlet

temperature for this unit is set at the factory to 195°F

(90.5°C). If you wish, you can also set a second or

“adjustable” limit setting that is lower.
Use the Up- and Down-Buttons to select the function, use

Up- and Down- to select the new value, then press the round

OK button.

Adjustable Stack Limit -
The absolute high limit setting for the stack for this unit is set

at the factory to 195°F (90.5°C). If necessary, you can set the

unit to use a second or “adjustable” limit setting that is lower.
Use the Up- and Down-Buttons to select the function, use

Up- and Down- to select the new value, then press the round

OK button.